DS200FHVAG1A is a High Voltage Gate Interface Board manufactured by General Electric as part of gas turbine control systems. It is a special-purpose board that provides the necessary SCR gate interface and cell voltage monitoring functions for the LCI power converter. The board dimensions are 3.25â and 5â wide and no power supplies are required. It operates in an ambient temperature environment of (32 - 122 F) plus (18 F). rise inside the cabinet. It provides an isolated path for gate power from the gate plus amplifier board to one 77mm SCR. Since the voltage drops across the SCR and sends a signal back to the FGPA. LED mounted on a board when SCR blocking voltage is present.
DS200FHVAG1A Circuit Details
This board includes circuitry to: Provide an isolated path for gate power from the Gate Pulse Amplifier (FGPA) board to one 77 mm SCR. When the voltage drop across the SCR exceeds a certain threshold, send a signal back to the FGPA. When an SCR blocking voltage is present, light an LED mounted on the board. This LED is used to indicate the presence of cell voltage.
A toroidal current transformer (CT) soldered to the board serves as the gate pulse transformer. The single-turn primary wire from the board can be centered in the CT window thanks to a hole in the board. Because of this design, the CT can withstand the electrostatic corona that surrounds power wiring.
This circuit rectifies the gate transformer's output, provides enough burden resistance to ensure good noise immunity, and connects to the SCR gate leads.
The FHVA board determines whether the SCR is in the OFF mode by sensing the presence of current in the 10K ohm equalizer resistor connected in parallel with the SCR.
The SCR Status Circuit also illuminates a red LED labeled C STAT to indicate the presence of blocking voltage. When the bridge power is turned on, the light from this LED should be visible, though it will dim slightly as the SCR conduction angle is increased.
DS200FHVAG1A Application Data
If the FHVA is powered on without an SCR gate connected to P1, pins P1-1 and P1-2 should be shorted together. This keeps resistors R1 and R2 from overheating.
If the FHVA board is left unconnected for an hour or more, insert a rubber plug in U1 to prevent dust accumulation on the lens.
DS200FHVAG1A Connections