Home     GE Turbine Control     GE Mark VI     DS200PTBAG1B

ProductS

DS200PTBAG1B

DS200PTBAG1B (GE Termination Board) features two terminal blocks, with 72 signal wires each, terminal posts for 6 signal wires, and contains three 10-pin connectors. JJR, JJT and JJS are the ID?s for the 10-pin connectors.?\n\nDS200PTBAG1B (LCI) is designed to process 7 different termination signals. DS200PTBAG1B (LCI) has over speed magnetic pickups, DS200PTBAG1B has flame detectors, DS200PTBAG1B has bus volts, DS200PTBAG1B has generator volts and current, DS200PTBAG1B has synchronizing, DS200PTBAG1B has protective inputs, and DS200PTBAG1B has alarm horn enable and disable hardware jumper location as termination signals.\n\nThe next steps should only be done if the power is removed from the drive ? be sure to have a narrow flat blade screwdriver to remove a signal wire from a terminal on a terminal block.\n\nAfter the power is removed, to detect the presence of power in the drive, use a tester. The components in the drive, like capacitors, hold power during normal drive operations. After waiting 30 seconds, you will notice the power in the components exit the drive. To avoid shock, before testing any components, use a tester.?\n\nUsing the terminal block ID and terminal numerical ID, locate the signal wire you want to remove. With a narrow screwdriver, loosen the terminal retention screw and pull the wire from the terminal. Be sure to mark the terminal ID the signal wire is connected to! In order to connect the signal wire, insert it into the terminal and tighten the terminal retention screw.?\n\nDS200PTBAG1B has bus volts, DS200PTBAG1B also has generator volts and current.?\n\nThe termination board, DS200PTBAG1B (LCI), is for the independent protective module core.
Product DESCRIPTION
Part Number
DS200PTBAG1B
Manufacturer
General Electric
Country of Manufacture
As Per GE Manufacturing Policy
Series
Mark V
Function
Module
Availability
In Stock
services we provide
Purchase Icon
Testing & Repair
Repair and Testing of circuit boards to diagnose ensure functionality to maintain current inventory and retain obsolete circuit boards/modules.
Exchange Icon
Training
Controls including HMI Training for Engineers, Technicians and Operators with wide variety of practical equipment including Management and Health & Safety.
Repair Icon
Purchase
You upgrade equipment and we purchase your surplus inventory to maximize the value of unused or end of life assets.
TECHNICAL SPECIFICATIONS FOR GE - DS200PTBAG1B

DS200PTBAG1B is a Protection Termination Board manufactured by General Electric as part of the Mark V LM Series used in gas turbine control systems. The P1 core's signals are terminated by the Protection Termination Module (PTBA), which is located in the core. In P1, input signals for high and low pressure shaft speeds, flame detection, generator and bus voltages, and generator currents land on the PTBA terminal board and are connected to the TCEB board. The R1 core is also connected to the speed signals.

DS200PTBAG1B Features

  • The PTBA terminal board reads external trip input signals, generator and bus signals, and generator breaker close signals before writing them directly to the Turbine Trip (TCTG) board in the P1 core. The PTBA terminal board is used to write trip output signals and generator breaker close signals from the TCTG board to the unit. Using a hardware jumper on the PTBA board, the TCEB board's audio alarm (horn) is powered. It has 2 3-pin connectors, 1 LED on the board's side, and 8 jumpers. Two 50-pin connectors and one block of ten LEDs are also included.
  • The LED on the board's side has the ID CR9. When illuminated, it is green in color and indicates that the board is getting electricity. The LED flashes to show that the board is processing information. A board that is not receiving power or not responding to voltage will not have an LED that is lighted. When the board is mounted in the rack cabinet between other boards, the LED is visible. From the window in the rack cabinet, you can see the LED.

DS200PTBAG1B Applications

  • For Primary Overspeed Defense The turbine speed sensor is usually connected to a pulse rate input on the PTBA terminal board in P1 core location 6.
  • HP and LP shafts are landed on the PTBA terminal board in the P1 core and written to the X and Y boards
  • in Emergency Overspeed Protection.
  • Flame Detection Circuits TCEA UV flame detector signals are fed into the PTBA board via the P1 core. These signals are read from the PTBA terminal board to the TCEB board via the JVA and JU connectors and written to the TCEA board via the JK (JKX/Y/Z) connectors.

DS200PTBAG1B Connectors

  • JJR - Writes the high and low pressure shaft speed signals to the TCQE board in the R1 core.
  • JM - In the P1 core, reads and writes the generator breaker signals (52GL) as well as the emergency trip outputs to and from the TCTG board.
  • JN - In the P1 core, reads and writes the generator breaker signals (G125P), writes the enable signal to the horn, and reads external trip signals to/from the TCTG board.
  • JU - Sends emergency overspeed, flame detect, and audible alarm (horn) enable signals to the TCEB board in the P1 core.
  • JV - In the P1 core, writes the generator and bus voltage signals, as well as the current signals (PT and CT), to the TCEB board.
  • JVA - Transports the 335 V dc from the TCEB board in the P1 core to the flame detection devices.
  • JJS/T - Not commonly used.

Hardware Configuration

J1 Enable the audible alarm (horn). Remove to silence.