Home     GE Turbine Control     GE Mark VI     ds200tcqbg1a

ProductS

ds200tcqbg1a

(RST) EXT ANALOG I
Product DESCRIPTION
Part Number
ds200tcqbg1a
Manufacturer
General Electric
Country of Manufacture
As Per GE Manufacturing Policy
Series
Mark VI/VIe
Function
Module
Availability
In Stock
services we provide
Purchase Icon
Testing & Repair
Repair and Testing of circuit boards to diagnose ensure functionality to maintain current inventory and retain obsolete circuit boards/modules.
Exchange Icon
Training
Controls including HMI Training for Engineers, Technicians and Operators with wide variety of practical equipment including Management and Health & Safety.
Repair Icon
Purchase
You upgrade equipment and we purchase your surplus inventory to maximize the value of unused or end of life assets.
TECHNICAL SPECIFICATIONS FOR GE - ds200tcqbg1a

DS200TCQBG1A is an RST Extended Analog I/O Board manufactured and designed by General Electric that functions as a processor board as part of the Mark V Series used in gas turbine control systems. Both a programmable logic device and EPROM modules are included in the board. The GE RST Extended Analog I/O Board additionally contains 15 jumpers, 1 OK LED that can be seen from the side, and 1 50-pin connector. When the OK LED on the side is lighted, it indicates that the board is receiving power. It also shows whether or not the board is processing. If the OK LED is off and the drive is powered on, it could be the first sign that there is a problem.

DS200TCQBG1A Functional Description

The following functions are defined by the TCQB configuration:

  • Proximitor inputs
  • Inputs for LVDT/LVDR
  • 2 outputs for regulator milliamps
  • LM input vibrations

When proximitors are needed, the card is used on Steam Simplex and in some TMR applications.

Proximitor Types

  • RF devices known as proximitor types generally measure the separation between an object and the device itself, such as the separation between a turbine shaft and a proximitor. A voltage signal that is inversely proportional to this distance is the device's output.
  • Changes in the AC component of the voltage are perceived as vibration, whereas changes in the DC component are interpreted as changes in position.

Proximitor Shaft Location

  • The input shaft speed for an algorithm is specified by Proximitor Shaft Location Assignments.
  • The three different shaft rotation speeds have different vibration frequency spectra. To obtain the first and second order vibration signal components, sampling is done at a frequency that is eight times the fundamental frequency.

Peak to Peak Vibration

  • The Proximitors use the AC signal component to indicate vibration.
  • Only this AC component is measured by the vibration inputs.

Transducer Sensitivity

  • The transducer determines the sensitivity of the transducer, which is measured in Volts/mil of vibration.
  • Generic Bently Nevada Position/Proximitor Probes or Differential Expansion Probes are the two different types of transducers. These values are prescribed by the Gas Turbine department.

Proximitor Low Limit Diagnostics & Proximitor High Limit Diagnostics

  • The operating range of the Bently Nevada proximitors is 0 to 20 V.
  • The probes, however, are only linear between 2 and 16 V. When used to detect vibration, any value outside of this range is non-linear and the device is regarded as failing.