Home     GE Turbine Control     GE Mark VI     ds2020expsg3

ProductS

ds2020expsg3

EXCITER POWER SUPPLY
Product DESCRIPTION
Part Number
ds2020expsg3
Manufacturer
General Electric
Country of Manufacture
As Per GE Manufacturing Policy
Series
Mark VI/VIe
Function
Module
Availability
In Stock
services we provide
Purchase Icon
Testing & Repair
Repair and Testing of circuit boards to diagnose ensure functionality to maintain current inventory and retain obsolete circuit boards/modules.
Exchange Icon
Training
Controls including HMI Training for Engineers, Technicians and Operators with wide variety of practical equipment including Management and Health & Safety.
Repair Icon
Purchase
You upgrade equipment and we purchase your surplus inventory to maximize the value of unused or end of life assets.
TECHNICAL SPECIFICATIONS FOR GE - ds2020expsg3

DS2020EXPSG3 is an exciter power supply board developed by GE under the EX2000 series. It generates the necessary signals for measuring alternating current and direct current input power. When the supply is powered by the station battery, it also acts as a current limiter. The automatic voltage regulators and excitation systems of the EX2000 series are used in a wide range of turbine-generator applications. The EX2000 Excitation Control System is a sophisticated platform for generator excitation.

Jumpers

JP1 identifies a manually moveable hardware jumper on the EXPS. JP1 connects the Tl secondary's center tap to ground.

DS2020EXPSG3 Board Replacement Procedure

  1. Switch off the power.
  2. To replace the EXPS board, the entire bulk power supply must be removed. Check for zero potential at all power supply assembly connections.
  3. To remove the power supply assembly, carefully disconnect the following connectors:
    1. Unplug the lFTB, 1TB-8TB, DCTB, VM2A, and VM2B connectors as needed.
    2. Disconnect the black and white wires on the CPS PTBl and PTB2 terminal boards. Unplug the ACPL.
  4. Remove the power supply assembly from the cabinet by carefully loosening the four assembly mounting screws. ACPL should not be removed.
  5. Transfer the assembly to a workbench and remove the four screws that hold the plastic protective cover in place. Unplug the DCPL, 3GDPL, and 4GDPL connectors from the EXPS board.
  6. Replace the old EXPS board with the new EXPS board. Set JPl on the replacement (new) board to the same position as on the board being replaced (old board).
  7. Reconnect the connectors that were removed in step 5. Replace the protective plastic cover and screws.
  8. Replace the power supply assembly in the cabinet. Reconnect the connectors that were removed in step 3.
    1. The cables are labeled with the connector name as it appears on the board. Reconnect all cables in the order they were removed. Check that the cables are properly seated on both ends.

DS2020EXPSG3 Features

  • The board is divided into three major components. A metal base with an attached circuit board, a second metal tier with an attached circuit board, and a plexiglass shield are among them. Each tier's circuit boards communicate with one another via surface-mounted electrical connections. The plexiglass shield is detachable and screws to the surface of the second layer. It has a prominent warning label that warns of the dangers of electrical shock or burns if the device is mistreated.