Home     GE Turbine Control     GE Mark VI     IS215UCVDH1A

ProductS

IS215UCVDH1A

UC2000/VME P233/1
Product DESCRIPTION
Part Number
IS215UCVDH1A
Manufacturer
General Electric
Country of Manufacture
As Per GE Manufacturing Policy
Series
Mark VI/VIe
Function
Module
Availability
In Stock
services we provide
Purchase Icon
Testing & Repair
Repair and Testing of circuit boards to diagnose ensure functionality to maintain current inventory and retain obsolete circuit boards/modules.
Exchange Icon
Training
Controls including HMI Training for Engineers, Technicians and Operators with wide variety of practical equipment including Management and Health & Safety.
Repair Icon
Purchase
You upgrade equipment and we purchase your surplus inventory to maximize the value of unused or end of life assets.
TECHNICAL SPECIFICATIONS FOR GE - IS215UCVDH1A

IS215UCVDH1A is a Mark VI controller module developed by General Electric. With additional modules and depending on whether the system is built as a simplex or TMR system, Mark VI can be scaled to fit the complexity and size of the related turbine system.

  • The component is powered by an AMD-K6 processor. This processor operates at 300 MHz and has 8 MB of flash memory. The controller is programmed to execute the turbine application code. It runs on the QNX operating system. Three front-faceplate communication ports connect to operator and engineering interfaces. Communication with HMIs and other control equipment via DH Ethernet connections
  • For setup purposes, an RS-232C connection via the COM1 port is used. Connection to the RS-232C port via the COM2 port for communication with the DCS (distributed control systems).
  • The board employs the VCMI communication board to transfer external data to and from the controller's control system database via the VME bus. An external clock interrupt allows the controller to stay within +/- 100 microseconds of the VCMI. The component employs control block language in conjunction with analog and discrete blocks.
  • The system supports Boolean, 16-bit/32-bit signed integer, and 32-bit/64-bit floating-point data types. COM port 1 is only used for diagnostics and operates at a 9600 baud rate. COM2 is used for serial Modbus communication and has a baud rate of 9600 or 19200.
  • Manufacturers' manuals and user guides can provide additional information about the board and its components.